The Lucy Electric Rapier GX, pole mounted, gas insulated load break switch is available up to 38 kV. The GX switch has been designed using SF6 puffer switching technology, delivering high performance and reliability. Whether operated as a simple, manually-independent switch or equipped with fully automated features, the GX switch is suitable for all sectionalising and network automation requirements.
Available in 17.5, 24, and 38 kV voltage ratings
Current rating of 630 A
Internal arc classification: Type C, 16 kA 1 second
Stainless steel tank sealed for life
Hook stick or motor operated
Suitable for any pole mounting
Independent spring operation, ensuring consistent opening and closing times
Optional internal VT for 15 kV version
Integration with remote terminal units for remote operation